    Air Conditioning Chilled Water Flow Measure Meter

    Ask Lasest Price
    Brand Name : Flo-Instru
    Model Number : ST501
    Certification : CE; ISO9001
    Payment Terms : T/T
    Delivery Time : 3-5 working days
    • Product Details
    • Company Profile

    Air Conditioning Chilled Water Flow Measure Meter

    ST501-PT100 Ultrasonic Energy Meter

    Clamp-on type ultrasonic energy meters for cooling and heating consumption measurement.


    Introduction

    ST501 is a high-accuracy ultrasonic flow meter with clamp-on transducers measuring big pipe diameter, which is built-in RTD module. When it is equipped with PT100 temperature sensor, ST501 can be upgraded into energy meter used for measuring individual energy consumption in any liquid heating/cooling systems. The meter is supplied complete with flowmeter and temperature sensor, which can makes the system real-time detect the temperature of supply and return pipe.

    The energy meter can be widely applied in various applications, like HVAC, cooling tower, data center, energy audit, and building(shipping mall, office, museum, hospital, school, subway etc.). Energy meter, also called thermal energy meter or heat meter, is used to accurately measure heat consumption in heating and cooling facilities so as to reach energy-saving and cost-saving.


    Benefits

    • Measures the actual flow and total consumption ofvarious liquids
    • No loss of process control, optimization of assets and efficiency, no downtime or expense from calibration
    • Adaptive signal processing algorithms optimize performance, ensuring accurate measurements even in challenging flow conditions.
    • Clear display interface and LCD display with alarm function, easy to operate and debug
    • Utilize transit-time ultrasonic technology so as to realize bidirectional flow measurement by precisely measuring the time it takes for ultrasonic signals to travel upstream and downstream
    • Leverage the data logging capabilities to analyze historical flow patterns to make system optimization.
    • Built-in keypad and simple menu system for fast and easy programming of pipe diameter, pipe material, liquid type, and measurement units.

    Principle

    • Introduction to TVT

    TVT(Transit-Time Vortex) technology represents a cutting-edge approach to ultrasonic flow measurement, combining the principles of transit-time ultrasonics with the capability to harness the vortex shedding phenomenon, delivering unparalleled accuracy and versatility in ultrasonic flow meters. This innovative integration technology enhances the accuracy, versatility, and performance of ultrasonic flow meters, making them well-suited for a wide range of applications across various industries and is a valuable solution for industries requiring precise flow measurements in varying flow conditions.


    • Enhanced Accuracy in Turbulent Flows:

    TVT technology excels in applications where fluid flow conditions vary between laminar and turbulent. The incorporation of vortex shedding data enhances accuracy in challenging flow environments.

    • Versatility in Fluid Types:

    TVT technology is versatile and suitable for a wide range of fluid types, including liquids with varying viscosities and densities.


    Specifications


    MeasurementGeneral Data
    FlowFlow Unit
    Velocity Rate0.03~±16ft/s(0.01 ~±5m/s)Support metric unit selection,
    Cubic Meters(m³),Liters(l),
    USA Gallons(gal)./hour,/min,The factory default unit is m³per hour.
    Accuracy+1.0%
    Repeatability0.3%
    Pipe SizeDN25~DN1200(1”"~48")
    LiquidWater,Sea water,Oil,Alcohol…Energy Unit
    Pipe MaterialCarbon Steel,Stainless Steel,PVC…Giga Joule (GJ),Kilocalorie (Kc),
    KWh,BTU
    Power Supply24 VDC
    Cable Length10mTotalizer
    Key Panel16(4×4)touch keys6 bit flow rate totalizer.
    Display20×2,alphanumeric,backlit LCDCommunication &Output
    Ambient Temp32°F~+140°F(0℃~60℃)ModBus RS485,4~20mA,
    Maximum load:750Ω
    OCT upper and lower limit alarm
    Fluid Temp.32°F~+140°F(0℃~60℃)
    PT100 Temp.Sensor32°F~257°F(0℃~125℃)
    Ambient HumidityRH 0~95%,No condensationHousing Material
    IP RateTransmitter:IP65Aluminum alloy
    Transducer:IP68